Issue 08/03
48 Quick Start Guide MICROMASTER 440
6SE6400-5GA00-0BP0
Parameter
Number
Parameter Description Suggested
Setting
User
Setting
P0309[0]
Enter Rated Motor Efficiency
(enter value from motor name plate)
If the setting is 0, the value is automatically calculated.
NOTE
You will not see this parameter in your BOP or AOP if
P0100=0.
Always enter the value from the motor name plate if you
have it. If this figure is calculated too low then you may
trip on F0041 (Motor ID Failure) or F0011 (Motor
Overtemperature).
From
Name
Plate
P0310[0]
Enter Rated Motor Frequency
(enter value from motor name plate)
NOTE
Typically this will already have been set by the DIP2(2)
switch, however if you have a non-standard motor, here
is where you enter the nominal frequency.
The number of pole pairs is automatically calculated
From
Name
Plate
P0311[0]
Enter Rated Motor Speed
(enter value from motor name plate)
If the setting is 0, the value is internally calculated.
NOTE
An entry must
be made for closed-loop Vector control,
V/f control with FCC and for slip compensation.
From
Name
Plate
P0320[0]
Enter Motor Magnetization Current
(enter value from motor name plate or data sheet)
If setting is 0, the value is internally calculated.
0
P0335[0]
Enter Motor Cooling Method*
0 Self-cooled using shaft mounted fan attached to
the motor
1 Force-cooled: Using a separately powered cooling
fan
0
P0500[0]
Enter Technological Application
0 Constant Torque
1 Pumps and Fans
3 Simple Positioning
NOTE
See P0205
0
www . ElectricalPartManuals . com