Appendix
A.1 Modbus TCP
PAC2200
102 Equipment Manual, 12/2019, L1V30415167B-03
A.1.4 Modbus-measured variables with function code "0x14"
Addressing the measured variables
The measured variables listed below can be read out via Modbus function code 0x14 "Read
File Record" in two steps.
Step 1 (File Number 1), preset to 10 s
Step 2 (File Number 2), preset to 15 min
Note
Error in the case of inconsistent access to measured values
Please ensure the start offset of the register is correct when making read accesses
.
Please ensure the start offset and the number of registers are correct when making write
accesses
.
Example: If a value consists of two registers, a read command applied in the second register
will generate an error code. The PAC2200 will also output an error code if a write operation
ends in the middle of a multi
-register value.
Abbr. in the "Access"
column
Abbreviations
R
Read access
W
Write access
RW
Read and write access
File
(FC0x14)
Offset
address
Address
FC0x03
FC0x04
Number
of
registers
Name
Format
Unit
Value range
Access
1
1
30001
2
Time stamp
unix_ts
-
R
1 3 30003 2 Flags uint32_t - 0= UNFLAGGED
1= FLAGGED
2= SAG
4= SWELL
8= POWER FAIL
R
1
5
30005
2
Voltage L1 - N
Float
V
R
1
7
30007
2
Voltage L2 - N
Float
V
R
1
9
30009
2
Voltage L3 - N
Float
V
R
1
11
30011
2
Voltage L1 - L2
Float
V
R
1
13
30013
2
Voltage L2 - L3
Float
V
R
1
15
30015
2
Voltage L3 - L1
Float
V
R
1
17
30017
2
Current L1
Float
A
R
1
19
30019
2
Current L2
Float
A
R
1
21
30021
2
Current L3
Float
A
R