A.1.11 Modbus command parameters
Addressing the command parameters
You can apply the Modbus function code 0x06 to the command parameters.
Table A- 13 Command parameters
Offset
Number
of r
egisters
Name
Unit
Format
Value range
Access
60004 1 Reset energy counter - unsigned
short
0 =
all
W
1 =
Active energy import tariff 1
2 =
Active energy import tariff 2
3 =
Active energy export tariff 1
4 =
Active energy export tariff 2
5 = Reactive energy import
tariff 1
6 = Reactive energy import
tariff 2
7 = Reactive energy export
tariff 1
8 = Reactive energy export
tariff 2
9 =
Apparent energy tariff 1
10 =
Apparent energy tariff 2
60005 1 Synchronization of the
demand period
Min. unsigned
short
1 ... 60 W
60006 1 Switching tariff - unsigned
short
0 =
Main tariff
W
1 =
Secondary tariff
60007 1 Acknowledge the diagnos-
tics bits
3)
(cf. stored bits in
unsigned long beginning
offset 205)
- unsigned
short
0 ... ffffh W
60008 1 Switching outputs (if pa-
rameterized)
- unsigned
short
0ffh ... 1ffh
W
Byte 0
= 0
Digital output 0.0
Byte 1
= 0
OFF
Byte 1
= 1
ON
60009 1 Switching command for
vector group
- unsigned
short
High 0 ... 99, Low 0 ... 1
High byte group assignment
Low byte 1 = ON, 0 = OFF
W
65300 1 Activation of IP / Ethernet
configuration
- unsigned
short
0 W
3) The Modbus Master must acknowledge these diagnostics bits.