Appendix
A.1 Modbus TCP
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
117
A.1.12 Modbus standard device identification with the function code 0x2B
Addressing the Modbus standard device identification
You can use Modbus function code 0x2B on these device identification parameters.
Table A- 14 Parameter for Modbus standard device identification
Firmware version / bootloader version
A.1.13 Active energy history with Modbus function code 0x14
The active energy counters listed below can be read out via Modbus function code 0x14
"Read File Record".
● The daily energy counter (file number 90) records the active energy for each day of the
preceding two months.
● The monthly energy counter (file number 91) records the active energy for each month of
the preceding two years.
90 1 32001 2 Error state Bool R
90 5 32005 2 Work portion today Tariff 1 Float R
Work portion today Tariff 2