EasyManua.ls Logo

Siemens SENTRON 7KM PAC2200 - Page 107

Siemens SENTRON 7KM PAC2200
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.1 Modbus TCP
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
105
File
(FC0x14)
Offset
address
Address
FC0x03
FC0x04
Number
of
registers
Name
Format
Unit
Value range
Access
1 537 30537 2 Minimum apparent pow-
er L2
Float VA R R
1 539 30539 2 Minimum apparent pow-
er L3
Float VA R R
1
541
30541
2
Minimum active power L1
Float
W
R
R
1
543
30534
2
Minimum active power L2
Float
W
R
R
1
545
30545
2
Minimum active power L3
Float
W
R
R
1 547 30547 2 Minimum reactive pow-
er L1
Float var R R
1 549 30549 2 Minimum reactive pow-
er L2
Float var R R
1 551 30551 2 Minimum reactive pow-
er L3
Float var R R
1
553
30553
2
Minimum power factor L1
Float
-
R
R
1
555
30555
2
Minimum power factor L2
Float
-
R
R
1
557
30557
2
Minimum power factor L3
Float
-
R
R
1
559
30559
2
Minimum frequency
Float
Hz
R
R
1 561 30561 2 Minimum average voltage
L - N
Float V R R
1 563 30563 2 Minimum average voltage
L - L
Float V R R
1
565
30565
2
Minimum average current
Float
A
R
R
1 567 30567 2 Minimum total apparent
power
Float VA R R
1 569 30569 2 Minimum total active pow-
er
Float W R R
1 571 30571 2 Minimum total reactive
power
Float var R R
1 573 30573 2 Minimum total power
factor
Float - R R
File
(FC0x14)
Offset
address
Address
FC0x03
FC0x04
Number
of
registers
Name
Format
Unit
Value range
Access
2
1
31001
2
Time stamp
unix_ts
-
R
2 3 31003 2 Flags uint32_t - 0= UNFLAGGED
1= FLAGGED
2= SAG
4= SWELL
8= POWER FAIL
R
2
5
31005
2
Voltage L1 - N
Float
V
R
2
7
31007
2
Voltage L2 - N
Float
V
R
2
9
31009
2
Voltage L3 - N
Float
V
R

Table of Contents

Related product manuals