Commissioning
6.3 Parameterizing the device
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
73
"Digital output" parameter
The following functions can be assigned to the "Digital output" parameter:
Energy pulse output; can be programmed for active or reactive energy pulses
Indication of the direction of rotation
Operating state display of the device
Switching output for remote control via the interface
Selection
Range
Factory setting
ACTION
OFF:
Output is deactivated.
DEVICE ON:
Output signals that the device is switched on.
REMOTE CONTROL
:
Output is controlled by remote access.
DIRECTION OF ROTATION:
Output is activated by a clockwise rotating electri-
cal field and remains active for as long as the field
is rotating in this direction.
PULSE:
Digital output signals the number of pulses set for
each energy unit (e.g. kWh). The energy counter
specified in the "COUNTER SOURCE" field is
evaluated here.
OFF
PULSES PER UNIT The "PULSES PER UNIT" property is only visible if
"PULSE INPUT" is set for the "ACTION".
Range: 1 to 4000
1
PRO
(Output pulse divider)
The "PULSES PER UNIT" property is only visible if
"PULSE INPUT" is set for the "ACTION".
Range: 1; 10; 100; 1000
1
UNIT Selects the type of cumulative power and the import
value that triggers the pulse when that value is
reached.
Counter Import Active Energy (kWh)
Counter Export Active Energy (kWh)
Counter Import Reactive Energy (kvarh)
Counter Export Reactive Energy (kvarh)
Counter Import
Active Energy
(kWh)
PULSE LENGTH The "Output pulse divider" property is only visible if
"Energy pulse" is set for the "USAGE TYPE".
Length of energy pulses.
Range: 30 ms to 500 ms
100 ms