Technical specifications
8.1 Technical specifications
PAC2200
84 Equipment Manual, 12/2019, L1V30415167B-03
Measuring inputs for voltage (5 A/65 A devices)
Measuring inputs
Voltage U
n (L-N / L-L)
100 V / 173 V AC, 50 / 60 Hz
230 V / 400 V AC, 50 / 60 Hz
(MID devices only 50 Hz)
Max. measurable voltage
Voltage L-N 230 V 3AC (+20%)
Voltage L-L
400 V 3AC (+20%)
Min. measurable voltage
Voltage L-N
100 V 3AC (-80%)
Voltage L-L
173 V 3AC (-80%)
Zero point suppression level
Voltage L-N
7 V
Voltage L-L
10 V
Impulse withstand voltage
6.5 kV (1.2 / 50 µs)
Measuring category
CAT III (acc. to IEC 61010-2-030)
Input resistance (L-N)
1
Measuring inputs for current (5 A device)
Only for connection to AC power systems via external current transformers (5 A device)
Measuring inputs
Rated current In I
e
1 A / 5 A
Max. permissible continuous current
10 A
Current impulse overload capability
100 A for 1 s
Zero point suppression level
10 mA / 45 mA
Measuring range
1 ... 120%
Measuring inputs for current (65 A device)
For direct connection to the AC system.
Measuring inputs
Reference current Iref (acc. to EN 50470-1)
10 A
Max. input current Imax
65 A
Current impulse overload capability
1990 A for 10 ms
Measuring range
0.5 ... 65 A