7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
99
Technical data
8
8.1 Technical data
PAC1600
Current
input (A)
Modbus
RTU
M-Bus S0 / Digital
output
MID Tariff input Accuracy
1
Weight
(g)
Single-phase devices
7KT1651
63
Class 1
148
7KT1652
63
Class B
148
7KT1653
63
Class 1
148
7KT1654
63
Class B
148
7KT1655
63
-
Class 1
148
7KT1656
63
Class B
148
Three-phase devices
7KT1661
5
Class 0.5s
332
7KT1662
5
Class B
332
7KT1663
5
Class 0.5s
332
7KT1664
5
Class B
332
7KT1665
80
Class 0.5s
360
7KT1666
80
Class B
360
7KT1667
80
Class 1
360
7KT1668
80
Class B
360
7KT1670
8
2
Class 1
360
7KT1671
80
2
Class B
271
7KT1672
5
2
Class 1
332
7KT1673
5
2
Class B
332
1
Accuracy active energy: (Versions without MID approval IEC/EN 62053-21/22. Versions with MID: EN 50470-3)
Input voltage
Nominal voltage of single-phase devices
230 V~
Nominal voltage of three-phase devices
230 V~/ 400 V~ L-L
Operating voltage range of single-phase devices
187 … 264 V~ L-N
Operating voltage range of three-phase devices
187 … 264 V~ L-N 323 … 456 V~ L-L
Nominal frequency of MID devices
50 Hz
Nominal frequency of non-MID devices
50/60 Hz
Operating frequency range
45 … 66 Hz