Commissioning
6.4 Modbus address register
7KT16 energy meter
82 Equipment Manual, 09/2020, 2514284147-04
4. Check the device parameters and adjust them if necessary.
Note
You can only change parameters in offline mode.
You can find more information on parameterization in the powerconfig Online Help.
5. In the "Parameters" window, click the "Load to device" button.
The set parameters are loaded to the device.
6.4 Modbus address register
6.4.1 Modbus address table for single-phase devices with Modbus interface
Continuous measured values
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format Access Unit Factor Measured variable
Hex Decimal
0002
2
2
UINT32
R
V
0.01
Voltage
0004
4
2
0006
6
2
0008
8
2
UINT32
R
A
0.001
Current
000A
10
2
000C
12
2
000E
14
2
0010
16
2
0012
18
2
0014
20
2
INT32
R
W
10.0
Active power
0016
22
2
0018
24
2
001A
26
2
INT32
R
var
10.0
Reactive power
Range limit
0026
38
2
INT32
R
0.01
Power factor
Range limit
0032
50
2
INT32
R
Hz
0.1
Frequency