3.5 Three-phase devices 5 A
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
51
3.5.4.3 Tariffs
In addition to the total and partial energies, two independent tariffs can be managed for
energy measurement.
The tariff is normally selected using the digital input but can be selected via the
communication protocol as an option.
The TAR-A input function is available for selecting the two tariffs. Activate the TAR-A input
function to make the selection shown in the table:
TAR-A
Tariff
ON
1
OFF
2
The device has a programmable AC voltage input.
The default function setting is TAR-A, which makes selection between tariffs 1 and 2
possible.
The text tAr-1 or tAr-2 flashes to indicate the selected tariff and the increasing counter
reading.
The counter readings for the tariffs are displayed as subpages of the system counters
(total and phase, if activated).
For devices with Modbus, you can select the active tariff using a special command in the
Modbus protocol. You can find more information in chapter Modbus address table for
three-phase devices 80 A with Modbus interface (Page 91).