Description
3.4 Three-phase devices 80 A
7KT16 energy meter
40 Equipment Manual, 09/2020, 2514284147-04
Defines the operating hours counter:
•
OFF = Hour counter deactivated. Nothing appears on the display.
ON =
The hour counter is incremented for as long as the energy meter measures
energy.
THR1 = The hour counter is incremented for as long as the limit threshold
defined by the parameters (P2-01 ... P2-06) is active.
THR2 = The hour counter is incremented for as long as the limit threshold
defined by the parameters (P3-01 … P3-06) is active.
INP = The hour counter is incremented for as long as the programmable input
is activated. Parameter P4.01 must be set to ON.
Activates the calculation and display of power demand values and max. demand
values.
3.4.4.6 Programmable AC input
Three-phase devices have a programmable AC input.
This input is deactivated by default. Set parameter P5.01 to select the required function.
You can use the input as follows:
• For 2 different tariffs (T1 and T2) with independent energy meters
• For resetting partial counters, hour counters and demand values
• For activating hour counters
3.4.4.7 Settable values for parameters P2.01, P3.01, P4.01
Setup Unit of meas-
Measured value
1)