3.3 Single-phase devices
7KT16 energy meter
20 Equipment Manual, 09/2020, 2514284147-04
5. Press the front key (> 3 s) to confirm and return to the parameter code selection.
ESC appears on the display after the last parameter code.
6. Press the front key (> 3 s).
The parameters are saved. The system resumes normal operation.
3.3.2 Advanced functions
Procedure
1. Press the front key from any display (> 5 s).
If password protection is activated, PASS appears on the display. Proceed to point 2
(password entry).
If password protection is deactivated, (factory setting, default password = 0000),
proceed to point 5 (function selection).
2. Release the key.
The device shows 0000 after approx. 2 to 3 seconds. The device is waiting for the
password to be entered.
3. Enter the password. Press the front key to increase the flashing digit in each case.
After 3 seconds, the entry field jumps to the next position.
4. After entering the password, press the front key to confirm.
If the password is incorrect, PASS Er appears on the display and the normal display
reappears.
If the password is correct, proceed to the next point.
5. The first entry in the following list of functions appears on the display:
CLEAR P: Clear partial energy meters
CLEAR h: Clear partial hour counter (if activated)
CLEAR d: Clear maximum demand values (if activated)
SETUP: Parameter programming (setup)
INFO: Revision and checksum of internal software
ESC: Return to normal display
Press the front key briefly to scroll through the list.
6. To select a function, press the front key for > 3 s while the function is visible on the display.
Note
If you keep the front key pressed for longer than 60 s, the menu closes automatically.