Commissioning
6.4 Modbus address register
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
91
6.4.3 Modbus address table for three-phase devices 80 A with Modbus interface
Continuous measured values
Modbus measured variables with the function codes 03 and 04
Address
Number
of regis-
ters
Format Access Unit Factor Measured variable
Hex Decimal
0002
2
2
UINT32
R
V
0.01
Voltage L1N
0004
4
2
UINT32
R
V
0.01
Voltage L2N
0006
6
2
UINT32
R
V
0.01
Voltage L3N
0008
8
2
UINT32
R
A
0.0001
Current L1
000A
10
2
UINT32
R
A
0.0001
Current L2
000C
12
2
UINT32
R
A
0.0001
Current L3
000E
14
2
UINT32
R
V
0.01
Voltage L1L2
0010
16
2
UINT32
R
V
0.01
Voltage L2L3
0012
18
2
UINT32
R
V
0.01
Voltage L3L1
0014
20
2
INT32
R
W
0.01
Active power L1
0016
22
2
INT32
R
W
0.01
Active power L2
0018
24
2
INT32
R
W
0.01
Active power L3
001A
26
2
INT32
R
var
0.01
Reactive power L1
001C
28
2
INT32
R
var
0.01
Reactive power L2
001E
30
2
INT32
R
var
0.01
Reactive power L3
0020
32
2
UINT32
R
VA
0.01
Apparent power L1
0022
34
2
UINT32
R
VA
0.01
Apparent power L2
0024
36
2
UINT32
R
VA
0.01
Apparent power L3
0026
38
2
INT32
R
0.0001
Power factor L1
0028
40
2
INT32
R
0.0001
Power factor L2
002A
42
2
INT32
R
0.0001
Power factor L3
002C
44
2
002E
46
2
0030
48
2
0032
50
2
UINT32
R
Hz
0.01
Frequency
0034
52
2
UINT32
R
V
0.01
Average Voltage LN
0036
54
2
UINT32
R
V
0.01
Average Voltage LL
0038
56
2
003A
58
2
INT32
R
W
0.01
Average Active power
003C
60
2
INT32
R
var
0.01
Average Reactive power
003E
62
2
UINT32
R
VA
0.01
Average Apparent power
0040
64
2
INT32
R
0.0001
Average Power factor

Table of Contents