Description
3.3 Single-phase devices
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
25
Explanations about the code
Setting 0000 (default) deactivates password protection.
Defines the function of the outputs depending on the device version.
100 PUL
… 1 PUL
function as pulse transmitters for active energy counting. These se-
lection options define the number of pulses transmitted for each kWh.
The digital output becomes an alarm threshold for the maximum or minimum limit,
depending on the values programmed
in P-04 and P-06.
P-04 > P-06:
– The output is activated if the value defined by P-03 is higher than P-04.
– The output is deactivated if its value is lower than P-06 (maximum limit with
hysteresis).
P-04 < P-06:
– The output is activated if the value defined by P-03 is lower than P-04.
– The output is activated if its value is higher than P-06 (minimum limit with
hysteresis).
Selects the measured variable.
Threshold value and delay for activation of the output.
The measurements are updated every 1 second.
Threshold value and delay for deactivation of the output.
Defines the operating hours counter:
•
OFF = Hour counter deactivated. The hour counter is not visible on the display.
ON = The hour counter is incremented for as lon
g as the energy meter measures
energy.
THR = The hour counter is incremented for as long as the threshold value
defined by the parameter (P-02, P-03, P-04 and P-05) is active.
Enables the calculation and display of the active energy requirement and the maxi-
mum demand.