3.4 Three-phase devices 80 A
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
35
For the variant with M-Bus interface
Code
Description
Default
Range
P8-01
Primary address
001
001 … 250
P8-02
Secondary address HIGH
Serial
number
0000 … 9999
P8-03
Secondary address LOW
Serial
number
0000 … 9999
P8-04
Baud rate
2400
300
600
1200
2400
4800
9600
19200
38400
Explanations about the code
P1-01
Setting
0000
(default) deactivates password protection. Every other setting defines
the password for access to advanced functions.
P1-02
Activate energy displays (export)
P2-01
Select code for comparison with threshold values for hour counter 1. You can find
more information in Settable values for parameters P2.01, P3.01, P4.01 (Page 40).
P2-02
Threshold for activation of hour counter 1. Note: The measurements are updated
every second.
P2-03
Threshold for deactivation of hour counter 1. The measurements are updated every
second.
P2-02 P2-03:
The hour counter is activated if the value defined by P2-01 is higher than
P2-02.
The hour counter is deactivated if its value is lower than P2-03 (maximum
limit with hysteresis).
P2-02 < P2-03:
The hour counter is activated if the value defined by P2-01 is lower than
P2-02.
The hour counter is deactivated if its value is higher than P2-03 (minimum
limit with hysteresis).
P3-01,
P3
-02,
P3-03
As with P2-01, P2-02 and P2-03, with reference to hour counter 2.
P4-01,
P4
-02,
P4-03
As with P2-01, P2-02 and P2-03, with reference to hour counter 3.