Description
3.5 Three-phase devices 5 A
7KT16 energy meter
56 Equipment Manual, 09/2020, 2514284147-04
P03 Password
• OFF
When OFF is set, the password setting is deactivated and access to settings and the
command menu is unrestricted. You can find more information in chapter
Com-
When P03.01 is active, value for specifying user access.
Similar to P03.02, administrator access.
P04 Integration
• Fixed
• Shift
• Bus
Integrated measurement calculation mode
•
Fixed
= The instantaneous measurements are integrated for the set time. Every
time this set time elapses, the integrated measurement is updated with the
result of the most recent integration.
Shift = The instantaneous measurements are integrated for a time = 1/15 of
the set time. Every time this interval elapses, the oldest value is replaced by the
newly calculated value. The integrated measurement is updated every 1/15 of
the set time. A time shift window with the 15 most recent calculated values
which correspond to the set time is taken into account here.
Bus = As a fixed mode; however, the integration intervals are defined by means
of synchronization commands sent on the serial bus.
Average (AVG) integration time of measurement for active, reactive and apparent
power.
Average (AVG) integration time of currents.
Average (AVG) integration time of voltages.
Average (AVG) integration time of frequency.