Configuration
4.10 Data points
SIMATIC CC7
104 Operating Instructions, 10/2019, C79000-G8976-C503-02
Operand area
The following operand areas of the CPU are available for S7:
I - Input
M - Memory
Q - Output
DB - Data block
The following areas (tables) of the station memory area are available for selection with
Modbus/TCP:
Discretes Input
Coil
Input Register
Holding Register
DB number
Number of the S7 CPU DB
Make sure that the number matches the actually configured number of the data block.
Offset / Address
Address of the operand depending on the data area
Enter the value as a decimal number:
Address (input, memory, output, DB)
Information for Bool operands in <Byte.bit>. E.g.: 0.6
Information for operands byte in <bytes>. E.g.: 3
Offset of the operand for the start address of the operand area (coil, tab)
Information in <bytes>. E.g.: 12
Length
Number of characters for the "String" data type (1 .. 254)
Access
The option specifies access of the communication partners to the gateway data.
Read
Only read access is permitted.
Read/write
Read and write access is permitted.
Write
Write access is permitted.