Circuit diagram example
4.4 TIA Portal configuration
Safety engineering with AS‑Interface in the SIMATIC ET 200SP, including typical circuit diagram
Function Manual, 08/2020, A5E44991382002A/RS-AB/002
31
4.4.3 Configuring ET 200SP System
In this example, an ET 200SP F-CPU is configured
with TIA Portal V15.1. In other versions, the representation may be slightly different; it then
applies analogously.
The steps shown apply correspondingly if an ET 200SP station is used with an interface
module (e.g. IM 155-6 PN ST) on a SIMATIC F-CPU (e.g. CPU 1515F-2PN). Alternatively to the
SIMATIC F-CPU, a fail-safe SINUMERIK controller can be used. The safety program is always
executed in the safe controller.
Configure the CM AS-i Master ST and F-CM AS-i Safety ST modules in the ET 200SP station.
Procedure:
1. Open your STEP 7-project in the TIA Portal.
2. Add your ET 200SP station from the hardware catalog.
3. Switch to the device view of the ET 200SP station.
4. Select the CM AS-i Master ST module from the ET 200SP folder in the "Hardware catalog"
window.
Communication module > AS-Interface > CM AS-i Master ST > 3RK7137-6SA00-0BC1.
Ensure that the selected version is the same as that of your device, otherwise update the
FW.
5. Drag & drop the selected AS-i Master to the next free slot of your ET 200SP station. The
CM AS-i Master ST module is plugged into a light base unit.
6. Select the F-CM AS-i Safety ST module from the ET 200SP folder in the "Hardware catalog"
window: Communication module > AS-Interface > F-CM AS-i Safety ST > 3RK7136-6SC00-
0BC1. Ensure that the selected version is the same as that of your device, otherwise update
the FW.
7. Drag & drop the selected F-CM AS-i Safety ST module directly to the right of the AS-i Master
in your ET 200SP station. Select a dark base unit for the F-CM AS-i Safety ST module.
8. Open the Properties window of the CM AS-i Master ST and switch to the AS-Interface tab in
the "General" area. Create a new AS-i network by clicking the "Add new subnet" button.

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O

Related product manuals