Wiring
4-11
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
4.3 Connecting the drive unit
To connect the connecting cables
Please note:
Note
Use only shielded twisted pairs for lines. The shielding must be connected to the
metallic or metallized connector jacket on the controller side. To protect the analog
setpoint signal against low-frequency interference, we recommend that you not
ground the shielding on the drive-unit side.
The cable set supplied as an accessory offers excellent immunity against interfer-
ence.
FM 353Connecting cable
X2
Drive device port
e.g. FM STEPDRIVE
Fig. 4-5 Connecting a drive unit
Procedure to connect the connecting cable
Connect the drive unit as follows:
1. Wire the free cable end of the connecting cable to the terminals of the drive
unit.
2. Open the front door and plug the sub-D connector into the module.
3. Lock the connector in place with the knurled screws. Close the front door.