Programming the Technological Functions
6-64
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
6.8 Error list, system messages (CPU)
The Table below lists some of the errors which occur during data transfer with the
internal SFC/SFBs (RET_VAL in SFCs 51, 58 and 59 and status messages (bytes
2 and 3), SFB 52/53, system messages) (see Reference Manual System Software
for S7-300/400; System and Standard Functions).
Table 6-12 Error list
Error Code (AW-DB, DBW66)
Description
HEX DEC INT
0 0 0 No errors
8082 32898 −32638 SZL_ID invalid or not in CPU
8085 32901 −32635 Information currently unavailable (caused by system)
80A0 32928 −32608 Negative acknowledgement when reading from module. Module re-
moved during Read operation or module defective.
80A1 32929 −32607 Negative acknowledgement while writing to module. Module removed
during Write operation or module defective.
80A2 32930 −32606
DP protocol error in layer 2 (data transfer over Profibus-DP interrupted,
e.g. due to wirebreak, missing terminator, parameterization error, etc.)
80A3 32931 −32605 S PROFIBUS: DP protocol error in layer 2 (data transfer over Profi-
bus-DP interrupted, e.g. due to wirebreak, missing terminator,
parameterization error, etc.)
S PROFINET IO: General CM error
80A4 32932 −32604 Communication problem on K bus
80A7 32935 −63601 DP slave or module is busy
80A9 32937 −63599 This function is not supported by DP slave or by the module.
80AA
to
80AF
32938
to
32943
−32598
to
−32593
DP slave or module is reporting a manufacturer−specific error in the
evaluation. For specifying the error, please refer to the Manufacturer
Documentation of the DP slave or of the module.
80B0 32944 −32592 The module does not know this data record.
80B1 32945 −32591 Invalid length specification in the RECORD parameter
80B2 32946 −32590 The configured slot is not occupied.
80B3 32947 −32589 Actual module type not the same as setpoint module type
80B5 32949 −32587 DP slave or module not ready
80B6 32950 −32586 Access to DP slave or module denied
80C0 32960 −32576 Module does not yet have the data to be read available
80C1 32961 −32575 Data from an identical Write job have not yet been processed on the
module
80C2 32962 −32574 Module is currently servicing the maximum possible number of re-
quests
80C3 32963 −32573 Needed resources (such as memory, etc.) are currently in use