Commissioning the device and device functions
4.4 Advanced device functions
SIMATIC IPC227E
52 Operating Instructions, 11/2016, A5E35782395-AB
Note
The EWF commands affecting the write protection do not become active until after the next
booting process.
Note
The EWF command
ewfmgr c: -commitanddisable cannot be used with the Live
options (i.e.
not like this: ewfmgr c: -commitanddisable live
).
Special features for the use of Enhanced Write Filters (EWF)
In the event of a power failure, if the EWF is enabled changes made after the boot
sequence on drive C: are lost.
To prevent data loss in the event of a power failure, the use of a UPS is recommended.
You can save the data in the EWF RAM overlay to the memory card or the hard disk
before you shut down the device. To do so, enter the following command in the command
prompt:
ewfmgr c: -commit
Note
When the system is set to automatically adjust the clock for daylight saving time adjustment,
systems
without central time management and with activated EWF set the clock forward or
backward by one hour in the daylight saving time or standard time period each time the
system boots.
The reason for this behavior is that Windows
Embedded Standard has a registry entry that
detects whether the clock has been adjusted for daylight saving time. Since this file is also
protected against modification by the EWF, the marker is lost during the boot sequence and
the adjustment is made again.
We therefore recommend that
you deactivate the automatic adjustment and change the
clock manually.
Follow these steps:
1.
Deactivate automatic adjustment in the Control Panel. In the "Time Zone" tab opened
with the menu command Start > Control Panel > Date and Time, remove the check mark
from the "Automatically adjust clock for daylight saving changes" check box.
2.
Save the change you have made with
ewfmgr c: -commit
and then reboot the system.

Table of Contents

Other manuals for Siemens simatic ipc227e

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic ipc227e and is the answer not in the manual?

Siemens simatic ipc227e Specifications

General IconGeneral
BrandSiemens
Modelsimatic ipc227e
CategoryIndustrial PC
LanguageEnglish

Related product manuals