S5-115F Manual Communications Capabilities
7.4.1 Settings on the CP 523 Module
The CP 523 module has a jumper header and a DIP switch. The following figure shows the position
of these components.
Figure 7-12. Location of Address Switch and Jumper Header on the CP 523 Module
9
Jumper header X10
a
a
a
a
a
a
a
a
a
a
a
a
1
Switch bank S1
for address
setting
OFF ON
8
1
Jumper X7: closed
Jumper X9: open
Jumper X8: open
Jumper X6: closed (from
Version 2 onward)
Jumper settings
There are nine jumpers in jumper header X10. The signal cables from the printed circuit board are
connected to the interface connector via these jumpers.
The 20 mA current supply of the active TTY interface is switched on with jumpers 1 and 2.
Jumpers 3 to 8 connect the signal cables of the RS-232-C (V.24) interface to the interface
connector. Jumper 9 connects the ground with the interface connector.
Note
Note the different safety characteristics of the TTY and RS-232-C (V.24) interfaces.
The current-driven TTY interface contains an optocoupler which guarantees reliable
galvanic isolation between the 220 V supply of the operator panel and the CP 523.
The voltage-driven RS-232-C (V.24) interface contains
no
such galvanic isolation.
EWA 4NEB 811 6148-02
7-35