S5-115F Manual Technical Specifications
8 Technical Specifications
8.1 General Technical Specifications
Climatic
Environmental Conditions
Temperature
Operating
- open design
Air intake temperature
(measured at the bottom
of the modules) 0 to+55° C
- cabinet design
(Where cabinet design is concerned, the dissipatible heat
loss depends on the type of construction, the ambient
temperature, and the arrangement of the devices.)
Air intake temperature
(measured at the bottom
of the modules) 0 to+55° C
Nonoperating - 40 to+85° C
Temperature change
- operating max. 10 K / h
- nonoperating max. 20 K / h
Relative humidity
- operating 95% (acc. to DIN 40040)
- nonoperating 95% (noncondensing)
Atmospheric pressure
- operating 860 to 1060 hPa
1
- nonoperating 660 to 1060 hPa
1
Pollutants
-SO
2
0.5 ppm,
(rel. humidity 60%,
noncondensing)
-H
2
S 0.1 ppm,
(rel. humidity 60%,
noncondensing)
Mechanical
Environmental Conditions
Vibration to IEC 68-2-6
- tested with 10 to 57 Hz,
(const. amplitude 0.15 mm)
57 to 150 Hz,
(const. acceleration 2 g)
Shock to IEC 68-2-27
- tested with 12 shocks
(half sine 15 g / 11 msec.)
Free fall to IEC 68-2-32
- tested with height of fall 1 m (3.3 ft.)
1 For use under 900 hPa (=1000 m above sea-level), check with the manufacturer on the cooling requirements.
EWA 4NEB 811 6148-02
8-1