I/O error without QVZ (message text Nos. 3851, 3852, 3853)
1st word Bits 12 - 15: 4
D
(Job number)
Bits 0 - 11: Message text number
2nd word In the high byte: Number of the I/O word
In the low byte: Number of the bit
3rd word Number of the signal group plus 3888
D
4th word In the high byte: Error-detecting program
In the low byte: Current error number
I/O error with QVZ (message text No. 3854)
1st word Bits 12 - 15: 4
D
(Job number)
Bits 0 - 11: Message text number
2nd word Where the QVZ is unspecifiable: 3872
D
In the case of QVZ on the DI module: 3873
D
In the case of QVZ on the DQ module: 3874
D
In the case of QVZ on the AI module: 3875
D
In the case of QVZ on the AQ module: 3876
D
3rd word Where the QVZ is unspecifiable: 255
D
For all other QVZs: Number of the I/O word
4th word In the high byte: Error-detecting program
In the low byte: Current error number
SINEC L1 error (message text No. 3846)
1st word Bits 12 - 15: 4
D
(Job number)
Bits 0 - 11: Message text number
2nd word Slave number
3rd word In the case of errors on the SINEC L1 LAN A: 65
D
= 41
H
In the case of errors on the SINEC L1 LAN B: 66
D
= 42
H
4th word No information All bits reset
All other errors
1st word Bits 12 - 15: 4
D
(Job number)
Bits 0 - 11: Message text number
2nd word In the high byte: Number of the I/O word
In the low byte: Number of the bit
3rd word No information: All bits reset
4th word In the high byte: Error-detecting program
In the low byte: Current error number