S5-115F Manual Rules Governing the Use of the S5-115F
Connecting sensors to analog input modules
S i n g l e -channel sensors must be permanently failsafe.
Subunit A Subunit B
AI
463 - 4U.
AI
463 - 4U.
Analog
value
sensor: V
0to1 V
0 to 10 V
All channels can be set by
jumpers
Figure 10-30. Type 16 AI, Safety-Related, Intermittent: Single-Channel Sensor with
Voltage Output
24 V
M
Subunit A Subunit B
AI
463 - 4U.
AI
463 - 4U.
Analog value
sensor: I
4 to 20 mA
0 to 20 mA
All channels can be set by
jumpers
Please note that the sensor must supply the current
for two loads!
Figure 10-31. Type 16 AI, Safety-Related, Intermittent: Single-Channel with Current
Output, Two-Wire Transducers
The use of two-wire transducers requires a dedicated power supply (wiring suggestion Fi-
gure 10-25).
EWA 4NEB 811 6148-02
10-47