Technical specifications
A.8 RTD and Thermocouple modules
Easy Book
324 Manual, 03/2014, A5E02486774-AF
RTD and Thermocouple (TC)
Isolation
Field to 24 VDC SM RTD and SM TC: 500 VAC
(Not applicable for SB RTD and SB TC)
24 VDC to logic SM RTD and SM TC: 500 VAC
(Not applicable for SB RTD and SB TC)
Channel to channel isolation
• SM RTD: None
(Not applicable for SB RTD)
• SM TC: 120 VAC
(Not applicable for SB TC)
Accuracy (25 °C / -20 to 60 °C) See the RTD/TC type tables:
• RTD (Page 326)
• TC (Page 324)
Maximum sensor dissipation
• RTD: 0.5 mW
• TC: Not applicable
Module update time See the RTD/TC filter selection tables:
• RTD (Page 327)
• TC (Page 325)
Cold junction error
• RTD: Not applicable
• TC: ±1.5 °C
100 meters to sensor max.
Wire resistance
• RTD: 20 Ω, 2.7 Ω for 10 Ω RTD max.
• TC: 100 Ω max.
Table A- 54 Thermocouple type (ranges and accuracy)
Normal range
3,
4
accuracy
@ 25 °C
Normal range
3, 4
accuracy
-20 °C to 60 °C
B 0.0 °C 200.0 °C 800.0 °C -- ±2.0 °C ±2.5 °C