EasyManua.ls Logo

Siemens SIMATIC S7 FH - Page 100

Siemens SIMATIC S7 FH
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming
Fail-Safe Systems
5-18 A5E00085588-03
Drivers for the F-I/Os in Standard Mode
If you use the F-I/Os in standard mode, you can use the standard channel drivers
from the PCS 7 Driver Blocks library.
Rules for F-Driver Blocks
The VALUE I/O of the F channel driver must be interconnected with the
symbolic address of the channel. In the case of redundant channels, the
VALUE I/O must be interconnected with the symbolic address of the channel
with the lower address .
A fail-safe signal on the ACK_REI input of each channel driver is required to
reintegrate an input or output channel. The signal must come from a fail-safe
digital input module or via the F_QUITES F block from an ES or OS.
Sequence: See Defining the Run Sequence.
Prerequisite
Symbolic names: Enter a symbolic name for each channel used. You must
allocate this name to the VALUE I/O of the associated F channel driver. We
recommend, for the sake of clarity, that you also enter the unused channels in the
symbol table as reserved or not used.
Procedure
When working with F-driver blocks, proceed as follows:
1. Insert the correct F channel driver for each configured input/output channel.
You only have to insert one F channel driver for each pair of redundant
channels.
2. Interconnect the VALUE I/O in each F channel driver with the symbolic name
of the associated channel. This step is required for all F channel drivers
placed. In the case of redundant modules, interconnect the VALUE I/O with the
lower channel address.
3. Interconnect the following with the required signals:
- the I inputs of the F channel drivers F_CH_DO
- the Q outputs of the F channel drivers F_CH_DI
- the V outputs of the F channel drivers F_CH_AI
These I/Os are F_BOOL or F_REAL types and should only be interconnected with I/Os of
the same type belonging to other fail-safe blocks.
4. Set the relevant ACK_NEC input to "1" if user acknowledgment is required with
automatic reintegration of the channel. The ACK_NEC input is preset with "0"
(optional, see "Passivation and Reintegration").
5. Optional: Evaluate the ACK_REQ output in the standard program or on the OS
to find out if user acknowledgment is required.

Table of Contents

Related product manuals