Fail-Safe Blocks
Fail-Safe Systems
8-70 A5E00085588-03
Error Information in Diagnostic Buffer
Error Code (W#16#...) Description
75DAH
Error in the safety data format (error due to online modification of the Safety
Program or internal CPU fault)
8.6.7 F_PLK
Function
This block executes, among other things, logical program and data flow control
before the output blocks and provides a corresponding enable signal for this.
The block is inserted automatically into each F-run-time group before the output
blocks at compilation.
The block output FAILED is for internal use only.
I/Os
Name Data Type Explanation Default
Outputs:
FAILED BOOL F-run-time group failure
indication
0
Error Handling
In the event of an error that is critical to safety, the system function SFC F_CTRL
is called. This records the event in the Diagnostic Buffer and requests a switch to
the reserve CPU if the error occurred only on the master CPU. For non-redundant
systems or a common-cause error occurring in both CPUs, the shutdown logic can
be configured to either disable the erred F-run-time group or the entire Safety
Program.
Error Information in Diagnostic Buffer
Error Code (W#16#...) Description
75DAH
Internal CPU fault
75E1H
Error during processing of F_CYC_CO
75E1H
Error during processing of F_TEST
75E1H
Error during processing of F_TESTC
75E1H
Internal CPU fault
75E1H
Error during program execution monitoring: error due to online modification of
the Safety Program or internal CPU fault