Getting Started
Fail-Safe Systems
2-4 A5E00085588-03
2.2 S7 F System - Getting Started
2.2.1 S7 F System, Setting up the Hardware
The following figure shows you an example of a hardware configuration.
Single-channel, one-sided
ET 200M Distributed I/O
S7 F programmable
controller
Fail-safe
signal modules
Profibus DP Cable
Safety Protector
Module
For this example, you need the following hardware components:
A programmable logic controller consisting of:
- 1 mounting rack (UR2-H)
- 1 power supply (PS 407 10A)
- 1 CPU 417-4H
An ET 200M distributed I/O device with an active backplane bus consisting of:
- 1 power supply (PS307 5A)
- 1 IM 153-2 Bus Interface Module
- 1 Safety Protector Module
- 1 fail-safe digital input module (SM 326F DI 24xDC24V)
- 1 fail-safe digital output module (SM 326F DO10xDC24V/2A)
Other accessories
- PROFIBUS cables and connectors
Set the DIL switches for the individual components as follows:
IM153-2 PROFIBUS address 3
SM 326F DI 24 Module address 8
(Only found on the reverse side; only in steps of 8)
SM 326F DO10 Module address 24
(Only found on the reverse side; only in steps of 8)