EasyManua.ls Logo

Siemens SIMATIC S7 FH - F_M_DO8

Siemens SIMATIC S7 FH
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fail-Safe Blocks
Fail-Safe Systems
8-64 A5E00085588-03
8.6.4 F_M_DO8
Function
The F module driver reads the digital output values from the associated F channel
drivers (F_CH_DO) and writes them to an 8-channel, fail-safe digital output
module. In addition, it reads the error information of the module and makes the
data available to the associated F channel driver (F_CH_DO).
If there is a redundant module, the digital values are written to both modules.
The F module driver is automatically inserted at the end of the run-time group
which also contains the associated F channel driver F_CH_DO. The I/Os of the F
module driver are automatically interconnected and supplied with values.
The outputs DIAG_1 and DIAG_2, at which error information is output, are
important.
I/Os
Name Data Type Explanation Default
Inputs:
CHADDR00 F_WORD Interconnection with the F
channel driver of channel 0
Interconnected
automatically
...
CHADDR07 F_WORD Interconnection with the F
channel driver of channel 7
Interconnected
automatically
CRC_IMP1 WORD CRC via implicit data SM1 Supplied
automatically
CRC_IMP2 WORD CRC via implicit data SM2
(only when RED = 1)
Supplied
automatically
TIMEOUT F_DINT Monitoring time in ms for vital-
sign monitoring
Supplied
automatically
RED F_BOOL Module Redundancy
0: SM configured as non-
redundant
1: SM configured as redundant
Supplied
automatically
LADDR INT Logical address of the module
(SM1)
Supplied
automatically
LADDR_R INT Address of the configured
redundant SM2 module (only
when RED = 1)
Supplied
automatically

Table of Contents

Related product manuals