Check Lists
Fail-Safe Systems
A-10 A5E00085588-03
A.4 Check List of the Safety Parameters of the F-Drivers
You must complete the following table at acceptance. The listed safety parameters
of the F driver blocks must be compared with the parameters of the F-I/Os from the
hardware configuration.
F Driver Type Safety Parameter Value Check
<Call of the F
driver block>
F_M_DI8,
F_M_DI24,
F_M_AI6,
F_M_DO10, or
F_M_D08
LADDR
LADDR_R
TIMEOUT, etc.
<Value from the
printout of the
Safety Program
information>
Example
F Driver Type Safety Parameter Value Check
F/1 F_M_DI8 TIMEOUT 1000
LADDR 24
LADDR_R 0
F/4 F_M_DI24 TIMEOUT 2000
LADDR 16
LADDR_R 0