Fail-Safe Blocks
Fail-Safe Systems
8-68 A5E00085588-03
Error Information in Diagnostic Buffer
Error Code (W#16#...) Description
75DAH
Error in the safety data format (error due to online modification
of the Safety Program or internal CPU fault)
8.6.6 F_M_AI6
Function
The F module driver reads the analog values (non-linearized values) and error
information of a 6-channel, fail-safe analog input module and makes the data
available to the associated F channel driver (F_CH_AI).
If there is a redundant module, the analog values of both modules are evaluated.
The F module driver is automatically inserted at the beginning of the run-time
group which also contains the associated F channel driver F_CH_AI. The I/Os of
the F block driver are automatically interconnected and supplied with values.
The outputs DIAG_1 and DIAG_2, at which error information is output, are
important.
I/Os
Name Data Type Explanation Default
Inputs:
CRC_IMP1 WORD CRC via implicit data SM1 Supplied
automatically
CRC_IMP2 WORD CRC via implicit data SM2
(only when RED = 1)
Supplied
automatically
TIMEOUT F_DINT Monitoring time in ms for vital-
sign monitoring
Supplied
automatically
MODE_00 F_WORD Measurement range coding,
channel 0
Supplied
automatically
...
MODE_05 F_WORD Measurement range coding,
channel 5
Supplied
automatically
RED F_BOOL Module Redundancy
0: SM configured as non-
redundant
1: SM configured as redundant
Supplied
automatically
LADDR INT Logical address of the module
(SM1)
Supplied
automatically
LADDR_R INT Address of the configured
redundant SM2 module (only
when RED = 1)
Supplied
automatically