Commissioning, service, troubleshooting   
13.2 Commissioning 
  SIMOCODE pro 
260  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
13.2.2  Commissioning with PROFINET 
13.2.2.1  PROFINET commissioning steps 
Please observe the information in Chapter General information about commissioning and 
service (Page 255). 
To commission SIMOCODE pro, proceed as follows: 
Table 13- 6  Commissioning the basic unit  
1  Switch on the power supply. In a fault-free state, the following LEDS should light up green: 
•  "Device" (lights up) 
•  "PORT 1 / PORT 2" when the PROFINET cable is connected (lighted or flashing). 
Continue with step 2. 
Otherwise, carry out diagnostics according to the LED display. For more information, see Chapter 
Diagnostics via LED display on the basic unit and on the operator panel (PROFINET) (Page 264
). Try to 
2  If you want to make SIMOCODE pro available to PROFINET, you must set the IP parameters and the 
PROFINET device names. For more information, see Chapter 
Setting IP parameters and PROFINET 
3  Parameterize SIMOCODE pro or check the existing parameterization, e.g. with a PC on which 
SIMOCODE ES (TIA Portal) software is installed. For this, connect the PC / PG to the system interface 
with the PC cable (see the figure below). 
 
 
Figure 13-2  Connecting a PC to the basic unit