Technical data   
15.8 Technical data of the operator panels 
  SIMOCODE pro 
360  System Manual, 05/2019, A5E40507475002A/RS-AD/004 
15.8  Technical data of the operator panels 
15.8.1  Technical data of the operator panel 
 
Technical data of the operator panel 
  Installation in a cabinet door or in a front panel, with IP54 system interface 
•  Red / green / yellow "DEVICE" LED  •  Red blocked: "Function test negative, device disabled" 
•  Green: "Ready for operation" 
•  Flashing green: "No connection to basic unit" 
•  Yellow: "Memory module or addressing plug detected" 
•  OFF: "No control supply voltage" 
•  Green "BUS" LED  •  Continuous light: "Communication with PLC/PCS" 
•  Flashing: "Baud rate recognized/communication with PC/PG" 
•  Red "GEN. FAULT" LED  •  Continuous light / 
•  Flashing: "Feeder fault," e.g. overload tripping 
•  3 yellow LEDs / 4 green LEDs 
For freely assigning any status signals 
•  Test / Reset  •  Resets the device after tripping 
•  Function test (system self-test) 
•  Operation of memory module or addressing plug 
•  Control buttons  •  For controlling the motor feeder, freely assignable 
•  Front 
For connecting a memory module, an addressing plug, or a PC cable for 
parameterization purposes 
•  Rear face 
For connecting a cable to the basic unit or the expansion module