Technical data
15.1 Common technical data
SIMOCODE pro
330 System Manual, 05/2019, A5E40507475002A/RS-AD/004
Shock resistance (sine pulse) acc. to IEC 60068-2-27
• General
• SIMOCODE pro S basic unit and
SIMOCODE pro S multifunction
module assembled on a current
measuring module
• SIMOCODE pro V basic unit
assembled on a current / voltage
measuring module
• 15 g / 11 ms
• 15 g / 11 ms
• 15 g / 11 ms
EMC stability according to IEC 60947-1
• IEC 60947-1, IEC 60947-5-1,
SN 27095, NE21
• DM-F: IEC 61326-3-1
Corresponds to degree of severity 3
Conducted interference, burst according
to IEC C 61000-4-4
2 kV (power ports)
Surge suppressor is required for inductive loads.
Conducted interference immission, high-
frequency according to IEC 61000-4-6
10 V
Conducted interference immission, surge
according to IEC 61000-4-5
2 kV (line to earth)
Electrostatic discharge, ESD according to
IEC 61000-4-2
4)
8 kV (air discharge)
3)
Radiated interference immission
according to IEC 61000-4-3
10 V/m
This is a Class A product. This product
can cause radio interference if used in a
domestic environment. Therefore, the
user may need to implement suitable
countermeasures.
Conducted and radiated interference
emission
DIN EN 55011/DIN EN 55022 (CISPR11/CISPR22)
(corresponds to Degree of Severity A)