Blocking Protection for Pumps with SIMOCODE pro V
Article ID: 109478058, V2.0, 09/2020
Counters
1. Define the following parameters under "Logic modules > Counter > Counter 1".
– Limit value: 4
– Input + (increment): Output TT 9 (truth table 9)
– Reset: Output TT 6 (truth table 6)
2. Define the following parameters under "Logic modules > Counter > Counter 2".
– Limit value: 65535
– Input + (increment): Output Timer 1
– Reset: Output Counter 2