Maintenance 
  9.3 Corrective maintenance 
1LA5/6/7/9, 1LG4/6, 1MA6/7, 1MB..1/2/3/4/5 - SH 63 ... 355 
Operating Instructions, 06/2018, A5E44455710A 
133 
Observe the documentation for tightening torques of the cable entries and sealing plugs for 
direct mounting at the machine as well as additional glands (e.g. adapters). 
 
Terminal boxes, end shields, grounding conductors, sheet metal fan covers 
If no other tightening torques are specified, then the values in the following table apply. 
Table 9- 4  Tightening torques for screws on the terminal box, end shields, screw-type grounding conductor connections 
 
max  1.2  3  5  9  24  42  70  165  340 
 
Terminal board and grounding 
Table 9- 5  Tightening torques for electrical connections on the terminal board and grounding 
 
 
Nuts or bolts that are mounted together with locking, resilient and/or force-distributing 
elements (e.g., safety plates, spring-lock washers, etc.) must be refitted together with 
identical, fully functional elements. 
Locking and sealing elements must always be replaced! 
 
●  Replace any corroded screws. 
●  Take care not to damage the insulation of live parts. 
●  Document the position of any rating and supplementary plates that have been removed. 
●  Avoid damaging the centering edges.