Electrical connection 
  6.4 Connecting the grounding conductor 
1LA5/6/7/9, 1LG4/6, 1MA6/7, 1MB..1/2/3/4/5 - SH 63 ... 355 
Operating Instructions, 06/2018, A5E44455710A 
77 
 
Cable entries, sealing plugs and thread adapters 
All cable entries and sealing plugs must be approved for use in the respective hazardous 
zone. 
●  Any openings that are not being used must be sealed using the appropriate certified 
sealing plugs. 
●  Please observe the manufacturer's specifications when fitting cable entries. 
Note the following when mounting: 
●  Avoid damaging the cable jacket. 
●  Adapt the tightening torques to the cable jacket materials. 
Observe the documentation for tightening torques of the cable entries and sealing plugs for 
direct mounting at the machine as well as additional glands (e.g. adapters). 
 
Connecting the grounding conductor 
The machine's grounding conductor cross-section must comply with EN / IEC 60034-1. 
Please also observe installation regulations such as those specified in EN / IEC 60204-1.  
Basically, there are two ways of connecting a grounding conductor to the machine. 
●  Internal grounding with a connection in terminal box at the location intended for this 
purpose and marked accordingly. 
●  External grounding with connection at the stator housing at the locations intended for this 
purpose and marked accordingly. 
 
Minimum surface area of grounding conductor 
Table 6- 3  Minimum cross-sectional area of grounding conductor 
Minimum cross-section of the phase conductor 
for installation 
S 
 
[mm²] 
Minimum cross-section of the associated ground-
ing connection 
 
[mm²] 
25 < S ≤ 50  25