Preparing for use   
4.8 Interlock circuit for anti-condensation heating 
  1LA5/6/7/9, 1LG4/6, 1MA6/7, 1MB..1/2/3/4/5 - SH 63 ... 355 
44  Operating Instructions, 06/2018, A5E44455710A 
Converter 
●  Always operate explosion-protected machines fed from converters with temperature 
sensors that directly monitor the temperature. 
●  Converter operation for these machines must be expressly certified. It is essential that 
you observe the specific manufacturer's information and instructions. Converter, machine 
and protective devices must be marked as belonging together and the permitted 
operating data must be defined in the common EC or EU-type examination certificate. 
 
Line supply 
●  Set the protective device (e.g. circuit breaker) to the rated current (see the rating plate). 
●  Or protect the machine using the certified temperature monitoring specified on the 
supplementary plate . 
Converter 
●  Always operate explosion-protected machines fed from converters with temperature 
sensors that directly monitor the temperature. 
 
Interlock circuit for anti-condensation heating 
If the anti-condensation heating is operated while the machine is running, this can increase 
the temperatures inside the machine.  
●  Install an interlock circuit that switches off the anti-condensation heating once the main 
machine is switched on.  
●  Only switch on the anti-condensation heating after the machine has been switched off. 
Switching on with the anti-condensation heating active (Page 103) 
 
 
Hearing damage when operating three-phase motors 
If the permissible sound pressure level is exceeded, hearing damage can occur when 
operating three-phase motors at their rated power. 
Observe the maximum permissible sound pressure level according to the ISO 1680 
standard. The maximum permissible sound pressure level is 70 dB (A).