Commissioning   
7.1 Measures before commissioning 
  1LA5/6/7/9, 1LG4/6, 1MA6/7, 1MB..1/2/3/4/5 - SH 63 ... 355 
92  Operating Instructions, 06/2018, A5E44455710A 
critical resistance value. Convert the value for the current winding temperature at the time 
of measurement, see above table. 
Measuring the polarization index 
1.  To determine the polarization index, measure the insulation resistances after one minute 
and ten minutes. 
2.  Express the measured values as a ratio: 
PI = 
R
insul 10 min
 / 
R
insul 1 min
 
Many measuring devices display these values automatically following the measurement. 
For insulation resistances > 5000 MΩ, the measurement of the PI is no longer meaningful 
and consequently not included in the assessment. 
 
Insulation in good condition 
< 2  Dependent on the complete diagnosis of the insulation 
 
 
If the critical insulation resistance is reached or undershot, this can damage the insulation 
and cause voltage flashovers.  
•  Contact the service center (Page 163). 
•  If the measured value is close to the critical value, you must subsequently check the 
insulation resistance at shorter intervals. 
Limit values of the anti-condensation heating insulation resistance 
The insulation resistance of the anti-condensation heating with respect to the machine 
housing should not be lower than 1 MΩ when measured at 500 V DC.  
 
Testing the cooling of the machine 
Cooling 
●  Check that the machine cooling is available for commissioning. 
Preparing for use (Page 33)