Installation 04/2005
SINAMICS G110 Operating Instructions
18 6SL3298-0AA11-0BP0
The serial numbers consist 13 characters and contains the date of manufacture,
e.g. XAP214-123456
XAP214-123456 Characters 1-2 are the site where the product is built
XAP214-123456 Character 3 denotes the year e.g. R = 2003
XAP214-123456 Character 4 is the month (1-9 =Jan-Sep, O =Oct, N =Nov, D =Dec)
XAP214-123456 Characters 5-6 are the day of the month
XAP214-123456 Character 7 is a separator
XAP214-123456 Characters 8-13 are the sequential serial number 1-999999
2.2 Power Losses
For information on the typical power losses for the SINAMICS G110 inverter,
please consult Table 7-6 on page 69.
2.3 Ambient operating conditions
Temperature
-10ºC to +50ºC (14ºF to 122ºF) see Table 7-8 on page 70 for derating information.
Humidity Range
95% Non-condensing
Altitude
If the inverter is to be installed at an altitude greater than 1000m, derating will be
required. Figure 2-2 below shows the permissible rated input voltages and output
current for inverter installations from 1000 m to 4000 m above sea level.
Figure 2-2 Derating for Altitude
Shock and Vibration
Do not drop the inverter or expose to sudden shock. Do not install the inverter in an
area where it is likely to be exposed to constant vibration.
Mechanical strength to EN 60721-3-3
¾ Deflection: 0.075 mm (10 … 58 Hz)
¾ Acceleration: 10 m/s
2
(58 … 200 Hz)
Electromagnetic Radiation
Do not install the inverter near sources of electromagnetic radiation.