SINAMICS G110 Specifications 04/2005
SINAMICS G110 Operating Instructions
68 6SL3298-0AA11-0BP0
Table 7-2 Control Terminals Screwless
Type – Wire Sizes
[mm
2
] 1
Minimum Cable Cross Section
[AWG] 18
[mm
2
] 1.5
Maximum Cable Cross Section
[AWG] 16
Table 7-3 Tightening Torques – Power Terminals
Power & PE Terminals
Frame Size Screw Type Nm lbf.in
FSA M3.5 0.96 8.50
FSB M4 1.50 13.30
FSC M5 2.25 19.91
Table 7-4 SINAMICS G110 Specifications, Frame Size A;
input voltage 1 AC 200 V – 240 V, ± 10 %, power range 120 W - 750 W
Frame Size A A A A A
[kW] 0.12 0.25 0.37 0.55
0.75
Motor Output Rating
[hp]
1
0.16 0.33 0.5 0.75 1.0
Order No. 6SL3211-
analog 0AB11-2UA0* 0AB12-5UA0* 0AB13-7UA0* 0AB15-5UA0* 0AB17-5UA0*
USS 0AB11-2UB0* 0AB12-5UB0* 0AB13-7UB0* 0AB15-5UB0* 0AB17-5UB0*
flat plate analog 0KB11-2UA0* 0KB12-5UA0* 0KB13-7UA0* 0KB15-5UA0* 0KB17-5UA0*
Unfiltered
flat plate USS 0KB11-2UB0* 0KB12-5UB0* 0KB13-7UB0* 0KB15-5UB0* 0KB17-5UB0*
analog 0AB11-2BA0* 0AB12-5BA0* 0AB13-7BA0* 0AB15-5BA0* 0AB17-5BA0*
USS 0AB11-2BB0* 0AB12-5BB0* 0AB13-7BB0* 0AB15-5BB0* 0AB17-5BB0*
flat plate analog 0KB11-2BA0* 0KB12-5BA0* 0KB13-7BA0* 0KB15-5BA0* 0KB17-5BA0*
Filtered
flat plate USS 0KB11-2BB0* 0KB12-5BB0* 0KB13-7BB0* 0KB15-5BB0* 0KB17-5BB0*
Output Current
2
[A] 0.9 1.7 2.3 3.2 3.9 (40ºC)
Input Current
3
[A] 2.3 4.5 6.2 7.7 10.0
[A] 10.0 10.0 10.0 10.0 16.0
Recommended Fuse
3NA3803 3NA3803 3NA3803 3NA3803 3NA3805
[mm
2
]
1.0 – 2.5 1.0 – 2.5 1.0 – 2.5 1.0 – 2.5 1.5 – 2.5
Input Cable
[AWG] 16 – 12 16 – 12 16 – 12 16 – 12 14 – 12
[mm
2
]
1.0 – 2.5 1.0 – 2.5 1.0 – 2.5 1.0 – 2.5 1.0 – 2.5
Output Cable
[AWG] 16 – 12 16 – 12 16 – 12 16 – 12 16 – 12
1
The horsepower (hp) ratings are obtained by comparison to the Siemens 1LA6 and 1LA7 motors and
not NEMA/UL rated motors.
2
Current data applies for an ambient temperature of 50ºC unless otherwise specified
3
The value applies to the rated mains voltage of 230 V
* Indicates the last digit of the Order No. may change due to modifications of hardware or software in
the product.