04/2005 Commissioning
SINAMICS G110 Operating Instructions
6SL3298-0AA11-0BP0
35
3.3.1 Factory Settings
The inverter has already been programmed at the factory for standard V/f
applications on a Siemens standard four-pole 3-phase induction motor, that has
the same power rating as the inverters.
Controlling the speed of the motor is accomplished by connecting the analog inputs
on the analog variant (switches and the potentiometer are not supplied with the
inverter) or via the RS485 connections on the USS variant as shown in Figure 3-3
below.
Figure 3-3 Basic operation – Analog and USS Variants
The inverter can be used with its default settings for a wide range of applications.
The default settings are shown in Table 3-1 (Analog variant) and Table 3-2 (USS
variant). The terminal layout is shown in Figure 3-3 above.
Note
The motor base frequency might have to be changed as described in the previous
section on page 34.
Table 3-1 Factory settings for operation using the standard inverter (Analog Variant)
Description Terminals Parameter Default Default Operation
Frequency Setpoint Source 9 P1000 = 2 Analog Input
Command Source 3,4 & 5 P0700 = 2 (see below)
Digital Input 0 3 P0701 = 1 ON/OFF1
Digital Input 1 4 P0702 = 12 Reverse
Digital Input 2 5 P0703 = 9 Fault Acknowledge
Control Method - P0727=0 Siemens Standard Control
With the default settings of the inverter (Analog variant) the following is possible:
¾ Start and stopping the motor (DIN0 via external switch)
¾ Reversing the motor (DIN1 via external switch)
¾ Fault Acknowledgement (DIN2 via external switch).