Commissioning 04/2005
SINAMICS G110 Operating Instructions
46 6SL3298-0AA11-0BP0
3.4.4 Quick Commissioning (P0010=1)
Quick commissioning is an easy way to optimally configure the SINAMICS G110
inverter to a specific motor. The motor data, taken from the motor rating label, is
entered into the inverter and then the inverter calculates the dependent control and
protection parameters.
An alternative to quick commissioning is parameter cloning (see page 49) that can
be used if a large number of inverters are to be commissioned to the same specific
motor.
NOTE
It is only possible to change motor parameters when quick commissioning is
enabled (P0010=1).
It is important that parameter P0010 is used for commissioning and P0003 is used
to select the number of parameters to be accessed. The P0003 parameter allows a
group of parameters to be selected that will enable quick commissioning.
Parameters such as Motor settings and Ramp settings are included.
At the end of the quick commissioning sequence, P3900 should be selected,
which, when set to 1, will carry out the necessary motor calculations and clear all
other parameters (not included in P0010=1) to the default settings. This will only
happen in the Quick Commissioning mode.
Parameter P0010 is automatically reset to the value 0 when P3900 > 0. The
inverter can only be run if P0010 has been set back to 0.
NOTE
We recommend commissioning is performed according to this scheme.
Nevertheless an expert user is allowed to perform the commissioning with the filter
functions of P0004.
Motor data for parameterization
Figure 3-6 below indicates where to find the relevant motor data on the motor
rating plate. Figure 3-6 is for illustration purposes only and the values within this
figure should not be keyed into your inverter, rather the values from your own
motor’s rating plate should be keyed into the inverter.
Figure 3-6 Typical Motor Rating Plate Example