Table 7-5 Frame Sizes B and C;
input voltage 1 AC 200 V – 240 V, ± 10 %, power range 1.1 kW - 3.0 kW
Frame Size B B C C
[kW] 1.1 1.5 2.2 3.0
Motor Output Rating
[hp]
1
1.5 2.0 3.0 4.0
Order No. 6SL3211-
analog 0AB21-1UA0* 0AB21-5UA0* 0AB22-2UA0* 0AB23-0UA0*
Unfiltered
USS 0AB21-1UB0* 0AB21-5UB0* 0AB22-2UB0* 0AB23-0UB0*
analog 0AB21-1AA0* 0AB21-5AA0* 0AB22-2AA0* 0AB23-0AA0*
Filtered
USS 0AB21-1AB0* 0AB21-5AB0* 0AB22-2AB0* 0AB23-0AB0*
Output Current
2
[A] 6.0 7.8 (40ºC) 11.0 13.6 (40ºC)
Input Current
3
[A] 14.7 19.7 27.2 32.0
[A] 20.0 25.0 35.0 50.0
Recommended Fuse
3NA3807 3NA3810 3NA3814 3NA3820
[mm
2
]
2.5 – 6.0 2.5 – 6.0 4.0 – 10 6.0 – 10
Input Cable
[AWG] 12 – 10 12 – 10 11 – 8 10 – 8
[mm
2
]
1.5 – 6.0 1.5 – 6.0 2.5 – 10 2.5 – 10
Output Cable
[AWG] 14 – 10 14 – 10 12 – 8 12 – 8
1
The horsepower (hp) ratings are obtained by comparison to the Siemens 1LA6 and 1LA7 motors and
not NEMA/UL rated motors.
2
Current data applies for an ambient temperature of 50ºC unless otherwise specified
3
The value applies to the rated mains voltage of 230 V
* Indicates the last digit of the Order No. may change due to modifications of hardware or software in
the product.
Table 7-6 Power losses SINAMICS G110
(230 V) inverters
Frame size Output Power
(kW)
Losses (W)
A 0.12 22
A 0.25 28
A 0.37 36
A 0.55 43
A 0.75 54
B 1.1 86
B 1.5 118
C 2.2 174
C 3 210
*The losses given in Table 7-6 are applicable for units fitted with 25 m of screened cable