04/2005 Commissioning
SINAMICS G110 Operating Instructions
6SL3298-0AA11-0BP0
39
NOTE
In some cases - when changing parameter values - the display on the BOP shows
. This means the inverter is busy with tasks of a higher priority.
Changing single digits in parameter values
For changing the parameter value rapidly, the single digits of the display can be
changed by performing the following actions:
1. Ensure you are in the parameter value changing level (see section
"Changing parameters with Basic Operator Panel" above).
2. Press
(function button), which causes the right hand digit to blink.
3. Change the value of this digit by pressing
or .
4. Press
(function button) again causes the next digit to blink.
5. Perform steps 2 to 4 until the required value is displayed.
6. Press the
to leave the parameter value changing level.
NOTE
The function button may also be used to acknowledge a fault condition.
Commissioning of motorpoti (MOP) function
Simple motor speed control can be achieved using the motorpoti (MOP) function of
the optional BOP (for using the MOP see also P1031 and P1040 in the Parameter
List).
The BOP motor control functions are disabled by default. To control the motor via
the BOP, the following settings must be completed (see also “Changing
parameters with the Basic Operator Panel“ above):
¾ P0719 = 11 (enables start/stop button on the BOP and enables the motor
potentiometer setpoint from the BOP).
Alternatively set:
P0700 = 1 (enables the start/stop button on the BOP).
P1000 = 1 (this enables the motor potentiometer setpoints).
1. Press the button to start the motor.
2. Press the
button while the motor is turning. Motor speed increases to
50 Hz.
3. When the inverter reaches 50 Hz, press button
. Motor speed and displayed
value are decreased.
4. Change the direction of rotation by pressing the
button.
5. Stop the motor by pressing the
button.
If the BOP has been set as the command source (P0700 = 1 or P0719 = 10 - 15),
the inverter will stop if the BOP is removed.