Commissioning 04/2005
SINAMICS G110 Operating Instructions
52 6SL3298-0AA11-0BP0
¾ Once the cloning procedure has started, it cannot be interrupted.
¾ It is possible to copy data from inverters of different power and voltage ratings.
¾ During download, if the data is not compatible with the inverter, the default
values for the parameter will be written to the inverter.
¾ During the cloning process any data already held by the BOP is overwritten.
¾ If the download or upload of data fails, the inverter will not function correctly.
Note
1. After cloning parameters between differing variants of the SINAMICS G110
inverters (i.e. Analog to USS or USS to Analog) the following parameter must
be checked:
¾ P0719 – Selection of command and frequency setpoint
¾ P1000 – Selection of frequency setpoint.
2. When cloning parameter sets associated with different firmware releases using
the BOP, it should be noted that for new parameters, the default value is
entered.