Functions   
7.9 Technological functions 
  Inverter with CU240B-2 and CU240E-2 Control Units 
202  Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA 
Table 7- 31  Control logic parameters of the motor holding brake 
Parameter  Description 
P1215 = 1  Enable motor holding brake  
0 Motor holding brake locked (factory setting)  
1 Motor holding brake just like the sequence control 
2: Motor holding brake permanently open 
3: Motor holding brake just like the sequential control, connected via BICO 
P1216  Motor holding brake opening time (factory setting 0.1 s) 
P1216 > Braking signal relay runtimes + Brake release time 
P1217  Motor holding brake closing time (factory setting 0.1 s) 
P1217 > Braking signal relay runtimes + Brake closing time 
P1226  Stationary state detection speed threshold (factory setting 20 1/min) 
When braking with OFF1 or OFF3, when the speed falls below this threshold, 
standstill is detected and the monitoring time P1227 or P1228 is started 
r0052.12  "Open motor holding brake" status 
 
Table 7- 32  Advanced settings 
Parameter  Description 
P0346  Magnetizing time (factory setting 0 s) 
During this time the induction motor is magnetized. The inverter calculates this 
parameter using P0340 = 1 or 3. 
P0855  Open motor holding brake (imperative) (factory setting 0) 
P0858  Close motor holding brake (imperative) (factory setting 0) 
P1227  Stationary state detection monitoring time (factory setting 300 s) 
P1228  Pulse deletion delay time (factory setting 0.01 s) 
P1351  Starting frequency of motor holding brake (factory setting 0%) 
Setting the frequency set value at the slip compensation output when starting with 
motor holding brake. 
When the parameter p1351 is set to > 0, slip compensation is automatically switched 
on. 
P1352  Starting frequency for motor holding brake (factory setting 1351) 
Setting the signal source for the frequency set value at the slip compensation output 
when starting with motor holding brake. 
P1475  Speed controller torque set value for motor holding brake (factory setting 0) 
Setting the signal source for the torque set value when starting with motor holding 
brake.