Commissioning
4.6 Back-up the settings and transfer
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
87
4.6.3 Backing up and transferring settings using BOP-2
Transferring parameters from the inverter to the operator panel (upload)
Start data transfer in the menu "OPTIONS" - "TO BOP".
Wait until the BOP-2 signals that data transfer has been completed.
Note
Data transfer can can take several minutes.
Transferring parameters from the operator panel to the inverter (download)
Start data transfer in the menu "OPTIONS" - "FROM BOP".
Wait until the BOP-2 signals that data transfer has been completed.
4.6.4 Saving setting on memory card
The memory card is a removable, non-volatile flash memory for all inverter parameters.
We recommend that you use one of the memory cards with the following order numbers:
MMC (order number 6SL3254-0AM00-0AA0)
SD (order number 6ES7954-8LB00-0AA0)
If you wish to use other SD or MMC memory cards, then you must format the memory card
as follows:
MMC: Format FAT 16
Insert the card into your PC's card reader.
Start a "command prompt" on your PC and enter the following: format x: /fs:fat
(x: Drive code of the memory card on your PC.)
SD: Format FAT 32
Insert the card into your PC's card reader.
Start a "command prompt" on your PC and enter the following: format x: /fs:fat32 (x:
Drive code of the memory card on your PC.)