Functions
7.9 Technological functions
Inverter with CU240B-2 and CU240E-2 Control Units
206 Operating Instructions, 07/2010, FW 4.3.2, A5E02299792B AA
Set the parameters of the automatic restart function.
The method of operation of the parameters is explained in the following diagram and in
the table.
)DXOW
&RXQWHUVWDUW
DWWHPSWV
$XWRPDWLF
DFNQRZOHGJHPHQW
&RXQWHULVGHFUH
PHQWHGE\
,IFRXQWHUWKHQIDXOW
)IROORZV
)DXOWDIWHU
SRZHUIDLOXUH
RULQRSHUDWLRQ
1HZIDXOW
&RXQWHU S
$XWRPDWLF21
FRPPDQG
0RWRUVSHHG
$VWDUWDWWHPSWPXVWEHVXFFHVVIXOZLWKLQWKLVWLPH
,IQRWIDXOW)IROORZV
$IWHUWKLVWLPHH[SLUHVWKH
LQYHUWHUUHVHWVWKHDWWHPSWHG
VWDUWVFRXQWHU
QGVWDUWDWWHPSW
VXFFHVVIXO
VWVWDUWDWWHPSW
XQVXFFHVVIXO
0RQLWRULQJWLPH
S>@
0RQLWRULQJWLPH
S>@
W
:
6XPRIWKHWLPHVIRUIO\LQJUHVWDUW
DQGPDJQHWL]LQJWLPHRIWKHPRWRU
W
W
W
W
W
W
W
VV
S S
W
:
W
:
1
The inverter automatically acknowledges faults under the following conditions:
p1210 = 1: always.
p1210 = 4 or 6: If the command to switch-on the motor is available at a digital input or via the
fieldbus (ON command = HIGH).
p1210 = 14 or 16: never.
2
The inverter attempts to automatically switch-on the motor under the following conditions:
p1210 = 1: never.
p1210 = 4, 6, 14 or 16: If the command to switch-on the motor is available at a digital input or via
the fieldbus (ON command = HIGH).
3
The start attempt is successful if flying restart has been completed and the motor has been
magnetized (r0056.4 = 1) and one additional second has expired without a new fault having
occurred.
Figure 7-17 Time response of the automatic restart